To download NI software, including the products shown below, visit ni.com/downloads.
Overview
This example shows how to add a custom scale to a LabVIEW VI.
Description
When adding a custom scale to a LabVIEW VI from MAX there are a few common problems. If you getthe following error,this is the way to fix it.
Error -200447 occurred at an unidentified location
Possible reason(s): Measurements: Units for the channel must be set to From Custom Scale when a custom scale is used with a channel. Notice the input on the create channel VI.
Requirements
Software
Hardware
Steps to Implement or Execute Code
**This document has been updated to meet the current required format for the NI Code Exchange.**
Example code from the Example Code Exchange in the NI Community is licensed with the MIT license.
the daqmx create channel actually has a terminal named 'units' from there you create a constant that says 'from custom scale' and you dont need to use the property node at all. this EPD does this: http://zone.ni.com/devzone/cda/epd/p/id/6062